M Code Output Function - Mitsubishi Electric MELSEC iQ-R-RD75P4 User Manual

Melsec iq-r series positioning module (application)
Table of Contents

Advertisement

M code output function

M code output function is used to command a subsidiary work (such as clamping, drilling, and tool replacement) related to the
positioning data being executed.
When M code ON signal [X4, X5, X6, X7] turns on during positioning, a number called an M code is stored in [Md.25] Valid M
code.
The value set in [Md.25] Valid M code is read from the CPU module, and used to command a subsidiary work. An M code can
be set for each positioning data. (Set the M code in [Da.10] M code, one of the setting items of positioning data.)
Output timing of M code ON signal
M code output function can set the output (storage) timing of M codes. (The M code is stored in [Md.25] Valid M code when M
code ON signal is turned on.)
The following two types of timing for outputting M codes are provided: WITH mode and AFTER mode.
■WITH mode
M code ON signal [X4, X5, X6, X7] turns on at the positioning start, and an M code is stored in [Md.25] Valid M code.
Positioning start signal
[Y10, Y11, Y12, Y13]
BUSY signal
[XC, XD, XE, XF]
M code ON signal
[X4, X5, X6, X7]
M code ON signal OFF
Cd. 7
request
Md. 25
Valid M code
Positioning
Da. 1
Operation pattern
*: m1 and m2 indicate set M codes.
■AFTER mode
M code ON signal [X4, X5, X6, X7] turns on at the completion of the positioning and an M code is stored in [Md.25] Valid M
code.
Positioning start signal
[Y10, Y11, Y12, Y13]
BUSY signal
[XC, XD, XE, XF]
M code ON signal
[X4, X5, X6, X7]
M code ON signal
Cd.7
OFF request
Valid M code
Md.25
Positioning
Operation pattern
Da.1
*: m1 and m2 indicate set M codes.
7 CONTROL SUB FUNCTIONS
280
7.9 Other Functions
ON
OFF
ON
OFF
ON
OFF
0
1 0
*
m1
V
01
ON
OFF
ON
OFF
ON
OFF
0
*
m1
V
01
0
1 0
*
m2
Dwell time
00
1
0
*
m2
00
t
t