Programming
To run AMA using the LCP
1.
By default parameter setting, connect terminals
13 and 27 before running AMA.
2.
Enter the Main Menu.
3.
Go to parameter group 1-** Load and Motor.
3
3
4.
Press [OK].
5.
Set motor parameters using nameplate data for
parameter group 1-2* Motor Data.
6.
Set motor cable length in parameter 1-42 Motor
Cable Length.
7.
Go to parameter 1-29 Automatic Motor Adaption
(AMA).
8.
Press [OK].
9.
Select [1] Enable complete AMA.
10.
Press [OK].
11.
The test runs automatically and indicates when it
is complete.
Depending on the power size, the AMA takes 3–
10 minutes to complete.
NOTICE
The AMA function does not cause the motor to run and
it does not harm the motor.