Parameter Descriptions; Parameters: 0-** Operation And Display - Danfoss VLT Midi Drive FC 280 Programming Manual

Hide thumbs Also See for VLT Midi Drive FC 280:
Table of Contents

Advertisement

Parameter Descriptions

4 Parameter Descriptions

4.1 Parameters: 0-** Operation and Display

0-01 Language
Select the language to be used in the display.
Option:
[0]
English
*
[1]
Deutsch
[2]
Francais
[3]
Dansk
[4]
Spanish
[5]
Italiano
[28]
Bras.port
0-03 Regional Settings
Option:
Function:
NOTICE
This parameter cannot be adjusted while
the motor is running.
[0]
Interna-
Activate parameter 1-20 Motor Power [kW] for
*
tional
setting the motor power in kW and set the
default value of parameter 1-23 Motor Frequency
to 50 Hz.
[1]
US
Activate parameter 1-20 Motor Power [kW] for
setting the motor power in hp and set the
default value of parameter 1-23 Motor Frequency
to 60 Hz.
0-04 Operating State at Power-up (Hand)
Option:
Function:
Select the operating mode upon
reconnection of the frequency converter to
mains voltage after power down in hand-on
mode.
[0]
Resume
Restart the frequency converter, maintaining
the start/stop settings (applied by [Hand On/
Off]) selected before the power-down of the
frequency converter.
[1]
Forced stop,
Restart the frequency converter with a saved
*
ref=old
local reference after mains voltage reappears
and after pressing [Hand On].
[2]
Forced stop,
Reset the local reference to 0 upon restarting
ref=0
the frequency converter.
0-06 GridType
Select the supply voltage, frequency, and type.
Option:
[0]
200-240V/50Hz/IT-grid
[1]
200-240V/50Hz/Delta
[2]
200-240V/50Hz
MG07C302
Programming Guide
0-06 GridType
Select the supply voltage, frequency, and type.
Option:
[10]
Function:
[11]
[12]
[20]
[21]
[22]
[100]
[101]
[102]
[110]
[111]
[112]
[120]
[121]
[122]
0-07 Auto DC Braking
Option: Function:
[0]
[1]
0-10 Active Set-up
Select the set-up to control the frequency converter functions.
Program parameters in set-ups 1–4. Use the factory set-up to
return the initial state. Use multi set-up for remote control.
Option:
[1]
[2]
[3]
[4]
[9]
0-11 Programming Set-up
Select the set-up to be programmed during operation; either the
active set-up or the inactive set-up. The set-up number being
edited flashes in the LCP.
Option:
[1]
[2]
[3]
Function:
[4]
[9]
Danfoss A/S © 07/2016 All rights reserved.
380-440V/50Hz/IT-grid
380-440V/50Hz/Delta
380-440V/50Hz
440-480V/50Hz/IT-grid
440-480V/50Hz/Delta
440-480V/50Hz
200-240V/60Hz/IT-grid
200-240V/60Hz/Delta
200-240V/60Hz
380-440V/60Hz/IT-grid
380-440V/60Hz/Delta
380-440V/60Hz
440-480V/60Hz/IT-grid
440-480V/60Hz/Delta
440-480V/60Hz
Protective function against overvoltage at coast in IT
grid environment. This parameter is active only when
[1] On is selected in this parameter, and IT-grid options
are selected in parameter 0-06 GridType.
Off This function is not active.
On
This function is active.
*
Set-up 1
*
Set-up 2
Set-up 3
Set-up 4
Multi Set-up
Set-up 1
Set-up 2
Set-up 3
Set-up 4
Active Set-up
*
Function:
4
Function:
Function:
23
4