Danfoss VLT Midi Drive FC 280 Programming Manual page 75

Hide thumbs Also See for VLT Midi Drive FC 280:
Table of Contents

Advertisement

Parameter Descriptions
8-43 PCD Read Configuration
Select the parameters to be assigned to the PCDs of the
telegrams. The number of available PCDs depends on the
telegram type. PCDs contain the actual data values of the
selected parameters.
Option:
[24]
[1660] Digital Input 18, 19, 27, 29,
32, 33
[25]
[1661] Terminal 53 Switch Setting
[26]
[1662] Analog Input 53(V)
[27]
[1663] Terminal 54 Switch Setting
[28]
[1664] Analog Input 54
[29]
[1665] Analog Output 42 [mA]
[30]
[1671] Relay Output [bin]
[31]
[1672] Counter A
[32]
[1673] Counter B
[33]
[1690] Alarm Word
[34]
[1692] Warning Word
[35]
[1694] Ext. Status Word
8-50 Coasting Select
Option:
Function:
Select control of the coasting function via the
terminals (digital input) and/or via the bus.
[0]
Digital
Activate coasting command via a digital input.
input
[1]
Bus
Activate coasting command via the serial
communication port or fieldbus option.
[2]
Logic AND Activate coasting command via the fieldbus/
serial communication port and 1 extra digital
input.
[3]
Logic OR
Activate coasting command via the fieldbus/
*
serial communication port or via 1 of the
digital inputs.
8-51 Quick Stop Select
Select the trigger for the quick stop function.
Option:
[0]
Digital input
[1]
Bus
[2]
Logic AND
[3]
Logic OR
*
8-52 DC Brake Select
Option:
Function:
Select control of the DC brake via the terminals
(digital input) and/or via the fieldbus.
NOTICE
When parameter 1-10 Motor Construction is
set to [1] PM non-salient SPM, only
selection [0] Digital input is available.
MG07C302
Programming Guide
8-52 DC Brake Select
Option:
[0]
[1]
Function:
[2]
[3]
*
8-53 Start Select
Option:
[0]
[1]
[2]
[3]
*
8-54 Reversing Select
Option:
[0]
[1]
[2]
[3]
*
Function:
8-55 Set-up Select
Option:
[0]
[1]
[2]
[3]
*
Danfoss A/S © 07/2016 All rights reserved.
Function:
Digital
Activate DC brake command via a digital input.
input
Bus
Activate DC brake command via the serial
communication port or fieldbus option.
Logic
Activate DC brake command via the fieldbus/
AND
serial communication port and additionally via 1
of the digital inputs.
Logic OR Activate DC brake command via the fieldbus/
serial communication port or via 1 of the digital
inputs.
Function:
Select the trigger for the start function.
Digital
A digital input triggers the start function.
input
Bus
A serial communication port or the fieldbus
triggers the start function.
Logic AND
The fieldbus/serial communication port and a
digital input trigger the start function.
Logic OR
The fieldbus/serial communication port or a
digital input triggers the start function.
Function:
Select the trigger for the reversing function.
Digital
A digital input triggers the reversing function.
input
Bus
A serial communication port or the fieldbus
triggers the reversing function.
Logic AND
The fieldbus/serial communication port and a
digital input trigger the reversing function.
Logic OR
The fieldbus/serial communication port or a
digital input trigger the reversing function.
Function:
Select the trigger for the set-up selection.
Digital
A digital input triggers the set-up selection.
input
Bus
A serial communication port or the fieldbus
triggers the set-up selection.
Logic AND
The fieldbus/serial communication port and a
digital input trigger the set-up selection.
Logic OR
The fieldbus/serial communication port or a
digital input triggers the set-up selection.
4