Troubleshooting

ALARM 95, Broken belt

Torque is below the torque level set for no load, indicating
a broken belt. Parameter 22-60 Broken Belt Function is set
for alarm.
Troubleshooting
Troubleshoot the system and reset the frequency
converter after clearing the fault.

ALARM 99, Locked rotor

The rotor is blocked. It is only enabled for PM motor
control.
Troubleshooting
Check if the motor shaft is locked.
Check if the start current triggers the current limit
set in parameter 4-18 Current Limit.
Check if it increases the value in
parameter 30-23 Locked Rotor Detection Time [s].

ALARM 126, Motor rotating

During AMA start-up, the motor is rotating. It is only valid
for PM motor.
Troubleshooting
Check if the motor is rotating before starting
AMA.

WARNING 127, Back EMF too high

This warning applies to PM motors only. When the back
EMF exceeds 90% x U
(overvoltage threshold), and
invmax
does not drop to normal level within 5 s, this warning is
reported. The warning remains until the back EMF returns
to a normal level.
ALARM 188, STO function fault
24 V DC supply is connected to only 1 of the 2 STO
terminals (37 and 38), or a failure in STO channels is
detected. Make sure that both terminals are connected to
24 V DC supply, and the discrepancy between the signals
at the 2 terminals is less than 12 ms. If the fault still occurs,
contact the local Danfoss supplier.