Discharge Time - Danfoss VLT Midi Drive FC 280 Programming Manual

Hide thumbs Also See for VLT Midi Drive FC 280:
Table of Contents

Advertisement

Safety
Power range
Voltage [V]
[kW (hp)]
200–240
0.37–3.7 (0.5–5)
0.37–7.5 (0.5–10)
380–480
11–22 (15–30)
Table 2.1 Discharge Time
WARNING
LEAKAGE CURRENT HAZARD
Leakage currents exceed 3.5 mA. Failure to ground the
frequency converter properly can result in death or
serious injury.
Ensure the correct grounding of the equipment
by a certified electrical installer.
WARNING
EQUIPMENT HAZARD
Contact with rotating shafts and electrical equipment
can result in death or serious injury.
Ensure that only trained and qualified personnel
perform installation, start-up, and maintenance.
Ensure that electrical work conforms to national
and local electrical codes.
Follow the procedures in this guide.
CAUTION
INTERNAL FAILURE HAZARD
An internal failure in the frequency converter can result
in serious injury when the frequency converter is not
properly closed.
Ensure that all safety covers are in place and
securely fastened before applying power.
MG07C302
Programming Guide
Minimum waiting time
(minutes)
4
4
15
Danfoss A/S © 07/2016 All rights reserved.
2
2
11

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents