Procedure 8-9 Problem: Cannot view alarms from a 5620 SAM on a
5620 NM or 1354 BM
Possible causes include incorrectly configured param.cfg parameters on the 5620 NM or
1354 BM to allow the forwarding of alarms to those platforms from the 5620 SAM.
1
2
3
4
5
6
7
8
8-10
Save the changes to the file.
Open a command tool on the 5620 NM or 1354 BM.
For:
a
The 5620 NM, navigate to the AS tool IM directory by typing:
/opt/netmgt/ALMAP/as/data/ascurim_0 ↵
b
The 1354 BM, navigate to the AS tool IM directory by typing:
/usr/Systems/1354BMETH_1/AS/data/ascurim ↵
Open the param.cfg file.
Ensure the NSP_USE_NSP and CORBA_SERVER_DISCOVERY parameters are
set to True.
Save the changes and close the file.
When the filters for CORBA are set to True, ensure the CORBA filter files are set
correctly.
For:
a
The 5620 NM, navigate to the AS tool IM configuration directory by typing:
/opt/netmgt/ALMAP/as/data/ascurim_0/ASIMconfig ↵
b
The 1354 BM, navigate to the AS tool IM directory by typing:
/usr/Systems/1354BMETH_1/AS/data/ascurim/ASIMFilter ↵
Ensure the following filters are set in the ASIMconfig or ASIMFilter files:
CORBA_ROOT_NAME_FILTER="*/*/AlarmSynchronizer*";
CORBA_ROOT_NAME_FILTER="*/*/EventChannelFactory*";
CORBA_ROOT_NAME_FILTER="*/*/X733EventChannel*";
Save the changes and close the file.