Outputs - Siemens MASS 2100 Operating Instructions Manual

Sitrans f coriolis flowmeters
Hide thumbs Also See for MASS 2100:
Table of Contents

Advertisement

Technical data

11.5 Outputs

● Zero adjust
– Starts the automatic zero point adjustment. This function employs the existing
● Reset totalizer
– Resets one of the internal totalizers 1, 2 or 3 (depending on configuration)
● Resets all totalizers simultaneously
● Freeze signal
– Freezes all currently measured values in the display and outputs
● Force signal
– Forces all outputs to adopt the value selected in the menu. If the value 100% is selected,
Changing polarity
Changing the polarity triggers the signal input to execute the set functionality.
11.5
Outputs
Table 11-13 Digital output
Description
Pulse
Resolution
Frequency
Resolution
Load
Time constant (adjustable)
Active
Passive
Functions
220
configurations and presumes that the process conditions are prepared for the zero point
adjustment routine
the current output will show 20 mA and the frequency output will show 10.000 kHz when
the external output is activated
WARNING
Channels 2 to 4
41.6 µs to 5 s pulse duration
1 μs
0 to 12.5 kHz, 50 % duty cycle, 120 % overscale provision
0.2 Hz
< 750 Ω
0 to 100 s
0 to 24 V DC, 87 mA, short-circuit-protected
3 to 30 V DC, 100 mA, short-circuit-protected
● Pulse
● Frequency
● Alarm class / NAMUR status
● Individual alarms
MASS 2100 & FC300 (FCT030)
Operating Instructions, 06/2017, A5E39789040-AA