Diagnosing and troubleshooting
10.2 Fault codes and corrective actions
ID/
Diagnostic
Icons
62
Fluid temp. below limit
63
Fluid temp. above limit
64
Frame temp. below limit
65
Frame temp. above limit
66
Standard Deviation' above limit
67
Zero Point Offset' above limit
68
Zero point adjustment failed
69
Empty Tube Limit' exceeded
70
Too little fluid in tube
192
Action
Increase the fluid temperature. If the failure con‐
tinues then contact your local Siemens repre‐
sentative
Reduce the fluid temperature. If the failure con‐
tinues then contact your local Siemens repre‐
sentative
Increase fluid temperature and check that ambi‐
ent temperature is within specified limits. If the
failure continues then contact your local Sie‐
mens representative
Reduce fluid temperature and check that ambi‐
ent temperature is within specified limits. If the
failure continues then contact your local Sie‐
mens representative
Measurement continues with values from last
successful zero point adjustment. Improve con‐
ditions for automatic zero point adjustment and
repeat adjustment.
Measurement continues with values from last
successful zero point adjustment. Improve con‐
ditions for automatic zero point adjustment and
repeat adjustment.
Measurement continues with values from last
successful zero point adjustment. Improve con‐
ditions for automatic zero point adjustment and
repeat adjustment.
Make sure that the sensor is filled with liquid and
that the liquid density is within the specified
'Empty Tube Limit'
Make sure that the sensor is filled with liquid
Comments
MASS 2100 & FC300 (FCT030)
Operating Instructions, 06/2017, A5E39789040-AA