Functions

8.12 SensorFlash

The diagnostic alarm list is default available in operating view 6.
There are two ways to have the alarms removed from the diagnostic list (menu item 3.2.2).
● Manual: The alarm remains in the diagnostic list until the alarm is manually acknowledged
(ack.).
The time of the acknowledgement is shown in the Diagnostic log (menu item 3.2.2) as long
as the log is not cleared.
● Auto: The alarm is removed from the Diagnostic log when the cause is removed (going)
8.11

Custom unit

Units can be defined/customized for all process values. This function can be used if the wanted
unit cannot be found in the list of units.
Custom unit is defined under each process value, and is available for mass flow, volume flow,
standard volume flow, density, fraction and medium temperature. Custom units menu is not
available in Custody transfer mode (CT).
8.12
SensorFlash
SensorFlash is a high-performance micro SD card (4 GB) with the ability to be updated by
inserting it in a PC. It is supplied with each sensor with the complete set of certification
documents including a calibration report. Material, pressure test, factory testing and order
conformance certificates are optional at ordering.
Further is contains parameter backup files, firmware logs, alarm history log, parameter change
log and data logging of process values and parameters.
The Siemens SensorFlash memory unit offers a permanent database with backup of all
parameter settings.
The SensorFlash supports copy and transfer of user settings from one flowmeter to another
to simplify commissioning. Only setup parameters are copied; no data are changed in the
receiving flowmeter.
Copying application setup from one device to another.
1. Remove the SensorFlash from the source device and insert the SensorFlash into the
destination device. The destination device disables the backup and signals an alarm.
2. Enter menu item Copy setups (1.8), select OK and press
move all the application setup parameters from the SensorFlash to the device. Backup is
still disabled and alarm signaled.
3. Remove the SensorFlash from the destination device and insert the original SensorFlash.
The device synchronizes the parameters to the SensorFlash and the alarm is cleared.
4. If there is no SD-card inserted: Insert SD-Card with backup data. Press right key to
continue...