Default settings
B.5 Inputs and outputs
HMI menu ID
Parameter
2.4.5.4.1
Process value
2.4.5.4.2
Direction
2.4.5.4.3
Loop current scale
2.4.5.4.4
Upper range value
2.4.5.4.5
Lower range value
2.4.5.4.6
Damping value
2.4.5.4.7
Fail-safe behavior
346
Description
Select process value for current
output.
Select measured flow direction.
The flow meter will only output
current when flow value is meas‐
ured in selected direction.
Assign process value to the
nominal upper range value
Assign process value to the
nominal lower range value
Set filter time constant. Defines
the damping of the current out‐
put signal. 0.0 means filter is off
Select current output reaction in
case of a fault.
Default value
Value range
[unit]
Mass flow
● Mass flow
● Volume flow
● Standard
volume flow
● Density
● Standard
density
● Medium
temperature
● Fraction A
● Fraction B
● Fraction A %
● Fraction B %
● Control valve
Positive
● Positive
● Negative
● Bidirectional
● Symmetric
● 4 to 20 mA
NAMUR
● 4 to 20 mA US
● 4 to 20 mA
(fault = 0 mA)
● 4 to 20 mA
● 0 to 20 mA
1)
1)
1)
1)
0 s
● 0 to 100 s
Lower fault cur‐
● Lower fault
rent
current
● Upper fault
current
● Last valid
value
● Current value
● Fail safe value
MASS 2100 & FC300 (FCT030)
Operating Instructions, 06/2017, A5E39789040-AA
Access
level
User
User
User
User
User
User
User