Functions
8.6 Inputs and outputs
Bidirectional flow across zero with positive scaling
①
②
③
④
⑤
⑥
⑦
⑧
⑨
Current output setting
● Process value = Massflow
● Direction = Bidirectional
● Current Mode = 4-20 mA US
● Upper Scaling = 400 kg/h
● Lower Scaling = -100 kg/h
● Fail Safe Mode = Minimum current
● Low-Flow Cut-Off = 25 kg/h
148
mA
Lower scaling
Low-flow cut-off
Upper scaling
Maximum measurement value
Upper range
Lower range
Minimum measurement value
Lower alarm value
Measurement range
Kg/h
MASS 2100 & FC300 (FCT030)
Operating Instructions, 06/2017, A5E39789040-AA