Installing/mounting

4.2 Installation instructions

4.1.2

Proper mounting

NOTICE
Incorrect mounting
The device can be damaged, destroyed, or its functionality impaired through improper
mounting.
● Before installing ensure there is no visible damage to the device.
● Make sure that process connectors are clean, and suitable gaskets and glands are used.
● Mount the device using suitable tools. Refer to the information in Construction
Loss of type of protection
Damage to device if the enclosure is open or not properly closed. The type of protection
specified on the nameplate or in Technical data (Page 215) is no longer guaranteed.
● Make sure that the device is securely closed.
4.2
Installation instructions
4.2.1

Sensor installation

4.2.1.1

Determining a location

Electromagnetic fields
Do not install the flowmeter in the vicinity of strong electromagnetic fields, for example near
motors, variable frequency drives, transformers etc.
Upstream / downstream
● No pipe run requirements, that is straight inlet/outlet sections are not necessary.
● Avoid long drop lines downstream from the sensor to prevent process media separation
causing air / vapor bubbles in the tube (min. back pressure: 0.2 bar).
● Avoid installing the flowmeter immediately upstream of a free discharge in a drop line.
40
(Page 230) for installation torque requirements.
CAUTION
CAUTION
MASS 2100 & FC300 (FCT030)
Operating Instructions, 06/2017, A5E39789040-AA