Siemens MASS 2100 Operating Instructions Manual page 201

Sitrans f coriolis flowmeters
Hide thumbs Also See for MASS 2100:
Table of Contents

Advertisement

ID/
Diagnostic
Icons
155
CH1
156
Safety validation state
157
Functional safety
158
CH1
159
Internal error
160
Mass flow
161
Volume flow
162
Density
163
Medium temperature
MASS 2100 & FC300 (FCT030)
Operating Instructions, 06/2017, A5E39789040-AA
Action
Loop current deviation. Check current output
cable connection. In passive mode check pow‐
er supply.
Finish proof test and confirm proof test passed,
or select skip proof test in menu "Functional
safety"
Device detected an event in safe operation. Ac‐
knowledge the safety event in menu Functional
Safety and repeat the safety commissioning. If
the error still exists, contact your local Siemens
representative.
Cable break. Check current output cable con‐
nection
Internal error in transmitter. Turn off the power,
wait 5 seconds and turn on the power again. If
the error still exists, contact your local Siemens
representative.
Value simulated. Disable 'Simulation' before re‐
turning to normal operation
Value simulated. Disable 'Simulation' before re‐
turning to normal operation
Value simulated. Disable 'Simulation' before re‐
turning to normal operation
Value simulated. Disable 'Simulation' before re‐
turning to normal operation
Diagnosing and troubleshooting
10.2 Fault codes and corrective actions