Status After Commissioning; Resetting Parameters To Factory Settings - Siemens SINAMICS DCM Operating Instructions Manual

Control module for variable-speed dc drives
Hide thumbs Also See for SINAMICS DCM:
Table of Contents

Advertisement

8.3.2

Status after commissioning

LOCAL mode (control via operator panel)
● You switch to LOCAL mode by pressing the "LOCAL/REMOTE" key.
● Control (ON/OFF) is carried out via the "ON" and "OFF" keys.
● You can set the setpoint using the "Increase" and "Decrease" keys or by entering the
8.3.3

Resetting parameters to factory settings

The factory settings represent the defined original status of the unit on delivery.
Resetting the parameters to the factory settings means that all the parameter settings made
since the system was delivered are reset.
Setting the parameter filter to "Parameter reset"
<MENU> <Commissioning/Service> <OK> <Device commissioning> <OK> <30: Parameter
Reset> <OK>
Restoring all parameters to their factory settings
All of the unit parameters are reset to their factory settings. The AOP30 is powered down
and back up again during this process.
SINAMICS DCM Control Module
Operating Instructions, 06.2010, C98130-A7067-A1-02-7619
appropriate numbers on the operation screen using the numeric keypad.
8.3 Commissioning using the AOP30 Operator Panel
Commissioning
209