Connection
(Connectors/Terminals)
Heat sink temperature (XT5, XT6)
Firing pulse transformer control
(XIMP_1 - XIMP11...16)
(XIMP_6 - XIMP21...26)
Firing pulses
(X11...X16, X21...X26)
Fuse monitoring equipment
(XS1_1...XS1_12 etc.)
Voltage sensing equipment (XU1,
XV1, XW1, XC1, XD1, etc.)
SINAMICS DCM Control Module
Operating Instructions, 06.2010, C98130-A7067-A1-02-7619
Cable
Single wires (stranded wires), twisted 10 m
2 x LiyCY 8 x 2 x 0.5 (or 1) mm
Or
Single wires (stranded wires),
twisted-pair
Single wires (short-circuit proof
cables), twisted-pair
Single wires (short-circuit proof
cables), installed in pairs (for each
fuse being monitored)
Single wires (short-circuit proof
cables),
U-V-W twisted, C-D twisted
Length
Notes
max.
Shield if >2 m.
10 m
Both ends of the shield have
2
to be connected.
3 m
Shield if >1 m.
3 m
Do not shield!
10 m
-
3 m
Please also refer to the
section titled "Connecting the
external power unit".
Connecting
6.5 Division options
85