Fuse Monitoring Equipment - Siemens SINAMICS DCM Operating Instructions Manual

Control module for variable-speed dc drives
Hide thumbs Also See for SINAMICS DCM:
Table of Contents

Advertisement

Connecting
6.16 Connector assignment (terminals, Faston mounting tabs, ribbon cables)
6.16.6

Fuse monitoring equipment

Connection type: Faston mounting tabs, 4.8 mm
Table 6- 21
Connections for fuse monitoring equipment
Connection
Function
XS1_1
Fuse 1
XS2_1
(1,000 V)
XS3_1
Fuse 2
XS4_1
(1,000 V)
XS5_1
Fuse 3
XS6_1
(1,000 V)
XS7_1
Fuse 4
XS8_1
(1,000 V)
XS9_1
Fuse 5
XS10_1
(1,000 V)
XS11_1
Fuse 6
XS12_1
(1,000 V)
XS1_2
Fuse 1
XS2_2
(575 V)
XS3_2
Fuse 2
XS4_2
(575 V)
XS5_2
Fuse 3
XS6_2
(575 V)
XS7_2
Fuse 4
XS8_2
(575 V)
XS9_2
Fuse 5
XS10_2
(575 V)
XS11_2
Fuse 6
XS12_2
(575 V)
XS1_3
Fuse 1
XS2_3
(250 V)
XS3_3
Fuse 2
XS4_3
(250 V)
XS5_3
Fuse 3
XS6_3
(250 V)
XS7_3
Fuse 4
XS8_3
(250 V)
XS9_3
Fuse 5
XS10_3
(250 V)
XS11_3
Fuse 6
XS12_3
(250 V)
XS1_4
Fuse 1
XS2_4
(125 V)
XS3_4
Fuse 2
XS4_4
(125 V)
XS5_4
Fuse 3
XS6_4
(125 V)
130
Technical data, comments
Measurement cables for the fuses to be monitored at a rated line
voltage >575 V to 1,000 V*)
Resistance between two associated connections: 388.4 kΩ **)
Measurement cables for the fuses to be monitored at a rated line
voltage >250 V to 600 V*)
Resistance between two associated connections: 196.4 kΩ **)
Measurement cables for the fuses to be monitored at a rated line
voltage >125 V to 250 V*)
Resistance between two associated connections: 100.4 kΩ **)
Measurement cables for the fuses to be monitored at a rated line
voltage >50 V to 125 V*)
Resistance between two associated connections: 52.4 kΩ **)
Operating Instructions, 06.2010, C98130-A7067-A1-02-7619