Modification to field extra-low voltage (50 V)
As part of the modification process, the resistors on field module A98043-A7116 must be
replaced:
Figure 6-29
R304, R306, R327 (220 kΩ): Replace with 5.6 kΩ
R308, R311, R314, R307, R310, R313, R328, R330, R333: Replace with 0 Ω or jumpers
Figure 6-30
All connection work must be carried out while the cabinet is de-energized. Failure to
connect correctly can lead to damage or destruction.
SINAMICS DCM Control Module
Operating Instructions, 06.2010, C98130-A7067-A1-02-7619
Field extra-low voltage (1)
Field extra-low voltage (2)
WARNING
Connecting
6.11 Field supply
107