Descriptions of functions
10.2 PROFIBUS
Bit
Meaning
9
Control request
"1" is always present
10
n setpoint reached or exceeded
Note:
The message is parameterized as follows: p50373 (threshold value), p50374 (hysteresis)
See FP8020 and FP2537
11
I or M limit not reached (when
p0922 = 1 or 352)
I or M limit not reached (when
p0922 = 20)
12
Holding brake released
(when p0922 = 1 or 352)
Reserved (when p0922 = 20)
13
Reserved
14
Motor rotates forward
(n_act ≥ 0)
15
Reserved
(when p0922 = 1 or 352)
CDS display
(when p0922 = 20)
Actual values
Actual speed value A 16-bit (NACT_A, NACT_SMOOTH)
● Actual speed value with 16-bit resolution incl. sign bit
● Bit 15 determines the actual value sign:
● The actual speed value is scaled using parameter p2000.
Actual current value (IAACT, IAACT_SMOOTH)
● Actual current value with 16-bit resolution
● The actual current value is scaled using parameter p2002.
318
0
Setpoint/actual value monitoring not within tolerance
band
1
Control request
0
Local operation
1
n setpoint reached or exceeded
0
n setpoint not reached
1
I or M limit not reached
0
I or M limit reached or exceeded
1
I or M limit not reached
0
I or M limit reached or exceeded
1
Holding brake is released
0
Holding brake is not released
1
Motor rotates forward (n_act ≥ 0)
0
Motor does not rotate forward (n_act < 0)
1
CDS selection bit 0 selected
0
CDS selection bit 0 not selected
– Bit = 0 → positive actual value
– Bit = 1 → negative actual value
N_act_A = 4000 hex or 16384 dec = speed in p2000
Ia_act = 4000 hex or 16384 dec = current in p2002
Explanation
Operating Instructions, 06.2010, C98130-A7067-A1-02-7619
BICO
BO: r0899.9
BO: r2199.1
BO: r1407.7
(inverted)
BO: 0056.13
(inverted)
BO: r0899.12
BO: r2197.3
BO: r0836.0
SINAMICS DCM Control Module