Table 9- 12
Inhibit type
No safety inhibit
Operator lock
Parameter disable
Operator inhibit lock + parameters disable
Settings
Figure 9-22
Setting safety inhibits
The "Operator inhibit lock" setting can be changed directly via <F5> ("Change") once you
have selected the selection box.
When "Parameters disable" is activated, you may enter a numeric password (twice). You
must also enter this password when deactivating "Parameters disable".
Operator inhibit lock (factory setting: Not active)
● Active: The parameters can still be viewed, but a parameter value cannot be saved
Parameters disable (factory setting: Not active)
● Active: Parameters cannot be changed unless a password is entered. Parameters are
Access level (factory setting: Expert):
The different parameters required for this complex application are filtered so that they can be
displayed as clearly as possible. You select them according to the access level.
An expert level, which must only be used by expert personnel, is required for certain actions.
SINAMICS DCM Control Module
Operating Instructions, 06.2010, C98130-A7067-A1-02-7619
Operator inhibit lock/parameters disable
(message: "Note: Operator inhibit lock active"). The OFF key (red) is enabled. The
LOCAL/REMOTE, ON (green), JOG, CW/CCW, INCREASE, and DECREASE keys are
disabled.
assigned in the same way as in the operator inhibit lock state. If you try to change
parameter values, the message "Note: Parameters disable active" is displayed. All the
control keys, however, remain enabled.
9.3 Controlling via the AOP30 operator panel
Online mode
Operation
Offline mode
303