Advertisement

Operation
9.2 Parameterizing using the BOP20 (Basic Operator Panel 20)
Drive object (DC_CTRL)
● p0010 Commissioning, parameter filter
9.2.2

Displays and using the BOP20

Features
● Operating display
● Changing the active drive object
● Displaying/changing parameters
● Displaying/acknowledging faults and alarms
● Controlling the drive using the BOP20
Operating display
The operating display for each drive object can be set using p0005 and p0006. Using the
operating display, you can change into the parameter display or to another drive object. The
following functions are possible:
● Changing the active drive object
● Parameter display
280
NOTICE
During a data save operation initiated by the user, the electronics power supply for the
SINAMICS DC MASTER must not be interrupted.
An active saving process is indicated by the following actions:
• The RDY LED flashes (see the "Description of functions" chapter, "Description of the
LEDs on the CUD" section)
• The BOP20 flashes
Interrupting the electronics power supply while saving can lead to the loss of the actual
unit parameter assignment. Also refer to the "Operation" chapter, "Memory Card
functions" section.
– Press key "FN" and "Arrow up" -> the drive object number at the top left flashes
– Select the required drive object using the arrow keys
– Acknowledge using the "P" key
– Press the "P" key.
– The required parameters can be selected using the arrow keys.
– Press the "FN" key -> parameter r0000 is displayed
– Press the "P" key -> changes back to the operating display