Commissioning
8.4 Commissioning with the STARTER commissioning tool
Entering the actual value source
Figure 8-23
⇒ Enter the type of tachometer or other actual value source. The drive cannot be operated if
no selection is made.
⇒ Enter the reference speed. To display on the AOP30 or to transfer the speed factors via
PROFIBUS, the physical speed at 100% is specified here.
⇒ Click Continue >
Encoder data - analog tachometer
⇒ Enter the tachometer voltage at maximum speed.
⇒ Click Continue >
226
Configuring the motor - specifying the actual value source
SINAMICS DCM Control Module
Operating Instructions, 06.2010, C98130-A7067-A1-02-7619