Commissioning
8.2 Commissioning using the BOP20 Operator Panel
〈5〉Enter the motor data
The motor data, as specified on the motor rating plate, must be entered in the following
parameters (see also the sections titled
"Speed-dependent current limitation"
Figure 8-1
p50100[D]
p50101[D]
p50102[D]
p50104[D]
p50105[D]
p50106[D]
p50107[D]
p50108[D]
p50109[D]
p50114[D]
〈6〉Data for actual speed value acquisition
〈6.1〉Operation with analog tachometer
p50083[D] = 1 The actual speed value comes from the "Main actual value" (r52013)
p50741[D]
198
Example of a rating plate
Rated armature current (in amperes)
Rated armature voltage (in volts)
Rated excitation current (in amperes)
Speed n1 (in rpm)
Armature current I1 (in amperes)
Speed n2 (in rpm)
Armature current I2 (in amperes)
Maximum operating speed n3 (in rpm)
1 = Speed-dependent current limitation active
Motor thermal time constant (in seconds)
channel
(terminals XT.103, XT.104).
Tachometer voltage at maximum speed (– 270.00 to +270.00 V)
Remark:
The value set here determines the 100% speed for the closed-loop speed
control.
"Thermal overload protection for the DC motor"
):
Operating Instructions, 06.2010, C98130-A7067-A1-02-7619
and
SINAMICS DCM Control Module