Siemens SINAMICS DCM Operating Instructions Manual page 74

Control module for variable-speed dc drives
Hide thumbs Also See for SINAMICS DCM:
Table of Contents

Advertisement

Connecting
6.4 Connecting the external power unit
Please refer to the next section for options on how to position the two plates and how the
unit can be divided.
The following electrical connections between the power unit (line voltage) and the
electronics must have short-circuit protection:
• Secondary sides of the firing pulse transformers
• Voltage measurement equipment
• Fuse monitoring equipment
Short-circuit protection measures must be implemented when laying these cables (which
carry a line voltage). The rms currents in the cables referred to are lower than 0.5 A.
• Method 1:
• Method 2:
74
WARNING
Short-circuit proof cables which burn from the inside when overloaded without bursting
their insulation
Cables protected as close to the power unit as possible with fuses. Fuses must have the
required cut-off capacity!
SINAMICS DCM Control Module
Operating Instructions, 06.2010, C98130-A7067-A1-02-7619

Advertisement

Table of Contents
loading

Table of Contents