Descriptions of functions

10.11 Speed controller

10.11
Speed controller
The speed controller is a PI controller with the following additional properties:
Start pulse
When starting the speed controller (i.e. when the controller is enabled) the I component can
start with a selectable value. This is necessary for suspended/hanging loads in order to
prevent the load from briefly sagging.
Adaptation
P gain and integral action time can be changed as a function of any signal (e.g. from the
speed actual value).
Droop
Droop (which can be switched in) can be implemented by feeding back the I component to
the input. As a consequence, the controller does not precisely control to the setpoint, but
permits a continuous setpoint-actual value deviation.
This is required, for example, if two drives are mechanically coupled with one another (e.g.
for a production machine where drives are coupled through the material web being
processed. In this case, the droop prevents that the two drives start to operate against one
another, although both operate with closed-loop speed control. In the case that a mechanical
connection is interrupted (e.g. if the material web breaks), then the speed of the drive
operating with droop only slightly changes.
Reference model
The reference model represents the P-controlled speed control loop and creates an
appropriately processed speed setpoint for the I-component. This means that the I-
component largely plays no role for setpoint changes, with the consequent improved,
overshoot-free response.
The reference model contains a PT2 element and a dead time element to emulate the
controlled system. See function charts 6810 and 6815.
Further, it is possible to feed in an external reference model (e.g. generated using DDC
function charts).
The reference model is set using the following parameters:
p50237 natural frequency
p50238 damping
p50239 deadtime
p50240 activation
The reference model is correctly set when the characteristics of the reference model output
(r52154) and the actual speed value (r52167) are virtually identical when the I-component of
the speed controller (p50224 = 0) is disabled.
390
SINAMICS DCM Control Module
Operating Instructions, 06.2010, C98130-A7067-A1-02-7619