4.2

Unit data

Table 4- 2
Technical data for SINAMICS DC MASTER Control Module
Armature
Measurable rated supply voltage
Electronics power supply
Rated supply voltage
Rated field supply voltage
Rated frequency
Rated field DC voltage
1)
Rated field DC current
Closed-loop control constancy
Degree of protection
Protection class
Dimensions
Weight
1)
2)
3)
SINAMICS DCM Control Module
Operating Instructions, 06.2010, C98130-A7067-A1-02-7619
1)
The field supply voltage may be below the rated field voltage (setting for p50078.1,
input voltages of up to 85 V are permitted). The output voltage decreases
accordingly.
This output voltage can no longer be achieved at voltages below 95% of the rated
supply voltage.
Conditions:
The closed-loop control (closed-loop PI control) constancy is related to the rated
motor speed and applies when the SINAMICS DC MASTER is at the operating
temperature. This is subject to the following preconditions:
• Temperature changes of ±10 °C
• Changes to the line voltage of +10% / – 5% of the rated input voltage
• Temperature coefficient of tachometer generator with temperature compensation:
0.15‰ every 10 °C (with analog tachometer generator only)
• Constant setpoint (14-bit resolution)
The option of operating with an extended frequency range can be provided on
request.
V
5.6 / 50 / 125 / 250 / 575 / 1000
V
18 to 30 V DC; In = 5 A
V
2-ph. 400 V AC (+15 % / -20 %)
2-ph. 480 V AC (+10 % / -20 %)
Hz
The units automatically adjust to the frequency of the applied
line voltage in a range from 45 to 65 Hz
V
Max. 325/375
A
40
Δn = 0.006% of rated motor speed during operation with
incremental encoder and digital setpoint
Δn = 0.1% of rated motor speed during operation with analog
tachometer or analog setpoint
IP00 acc. to DIN EN 60529
Class I (with protective conductor system) and class III (PELV)
to EN 61800-5-1
For dimension drawings, see Chapter 5.
kg
12
Technical data
4.2 Unit data
.
3)
2)
35