Note
If BICO interconnections exist between drive objects, all interconnected objects must be
configured.
• Example:
Note
Only those messages which are listed in the indexed parameters can be changed as
desired. All other messages retain their factory settings or are reset to the factory settings.
Examples:
• In the case of messages listed via p2128[0...19], the message type can be changed. The
• The fault response of fault F12345 has been changed via p2100[n]. The factory settings
Triggering on messages (example)
Select message
p2128[0] = 1001
or
p2128[1] = 1002
Note
The value from CO: r2129 can be used as a group trigger.
CO: r2129 = 0 No selected message has been output.
CO: r2129 > 0 Group trigger.
At least 1 selected message has been output.
The individual binector outputs BO: r2129 should be investigated.
Triggering messages externally
If the appropriate binector input is interconnected with an input signal, fault 1, 2, or 3 or alarm
1, 2, or 3 can be triggered via an external input signal.
Once an external fault (1 to 3) has been triggered on the Control Unit drive object, this fault
is also present on all associated drive objects. If one of these external faults is triggered on a
different drive object, it is only present on that particular drive object.
SINAMICS DCM Control Module
Operating Instructions, 06.2010, C98130-A7067-A1-02-7619
The TM31 has BICO interconnections with the drive and F35207 is to be reconfigured as
an alarm.
– p2118[n] = 35207 and p2119[n] = 2
– This must be set for TM31 and the drive.
factory setting is set for all other messages.
are to be restored.
– p2100[n] = 0
Trigger signal
BO: r2129.0
BO: r2129.1
Descriptions of functions
10.28 Diagnostics
457