Area Range Compare - Zcp(88) - Omron SYSMAC C200HS Operation Manual

Programmable controllers
Hide thumbs Also See for SYSMAC C200HS:
Table of Contents

Advertisement

Data Comparison
Example
00000
CD: 001
001 0210
Compare the data in IR 001
with the given ranges.
5-17-6 AREA RANGE COMPARE – ZCP(88)
Limitations
Description
176
The following example shows the comparisons made and the results provided
for TCMP(85). Here, the comparison is made during each cycle when 00000 is
ON.
TCMP(85)
001
HR 10
HR 05
Upper limits
HR 10
0100
HR 11
0200
HR 12
0210
HR 13
0400
HR 14
0500
HR 15
0600
HR 16
0210
HR 17
0800
HR 18
0900
HR 19
1000
HR 20
0210
HR 21
1200
HR 22
1300
HR 23
1400
HR 24
0210
HR 25
1600
Ladder Symbols
ZCP(88)
CD
LL
UL
LL must be less than or equal to UL.
When the execution condition is OFF, ZCP(88) is not executed. When the exe-
cution condition is ON, ZCP(88) compares CD to the range defined by lower limit
LL and upper limit UL and outputs the result to the GR, EQ, and LE flags in the
SR area. The resulting flag status is shown in the following table.
Comparison result
p
CD < LL
LL ≤ CD ≤ UL
UL < CD
Address
Instruction
00000
LD
00001
TCMP(85)
R: HR 05
HR 0500
0
HR 0501
0
HR 0502
1
HR 0503
0
HR 0504
0
HR 0505
0
HR 0506
1
HR 0507
0
HR 0508
0
HR 0509
0
HR 0510
1
HR 0511
0
HR 0512
0
HR 0513
0
HR 0514
1
HR 0515
0
Operand Data Areas
CD: Compare data
IR, SR, AR, DM, HR, TC, LR, #
LL: Lower limit of range
IR, SR, AR, DM, HR, TC, LR, #
UL: Upper limit of range
IR, SR, AR, DM, HR, TC, LR, #
Flag status
GR (SR 25505)
EQ (SR 25506)
0
0
0
1
1
0
Section 5-17
Operands
00000
001
HR
10
HR
05
LE (SR 25507)
1
0
0

Hide quick links: