Sensor Input Settings And Indicator Range - Omron E5EZ-PRR User Manual

Position proportional controller
Hide thumbs Also See for E5EZ-PRR:
Table of Contents

Advertisement

Appendix

Sensor input settings and indicator range

E5EZ-PRR2 □ T
Input type Specifications
Thermocouple
Platinum
/multi input type
resistance
platinum
thermometer
resistance
thermometer
Thermocoupl
e
Non-contact
temperature
sensor ES1B
Analog signal
input
E5EZ-PRR2 □ L
Analog Input type
Current
Input
Voltage
Input
Thermocouple/multi input type platinum resistance thermometer initial value is 「5」 , analog input type is 「0」 .
Input type specifications are given below:
K: GB/T 2814-98
E: GB/T 4993-98
S: GB/T 3772-98
Control range
Platinum resistance thermometer and thermocouple input temperature setting lower limit -20°C~ temperature upper limit+20°C or
temperature setting lower limit -40F~ temperature setting upper limit+40F.
ES1B input type has the same input indicator range.
Analog input indicator range -5%~105%.
A-10
Setting
value
Pt100
0
-200~850 ( °C )
1
-199.9~500.0 ( °C ) /-199.9~900.0
2
0.0~100.0 ( °C )
JPt100
3
-199.9~500.0 ( °C ) /-199.9~900.0
4
0.0~100.0 ( °C )
K
5
-200~1300 ( °C )
6
-20.0~500.0 ( °C ) /0.0~900.0 ( °F )
J
7
-100~850 ( °C )
8
-20.0~400.0 ( °C ) /0.0~750.0 ( °F )
T
9
-200~400 ( °C )
22
-199.9~400.0 ( °C ) /-199.9~700.0
E
10
0~600 ( °C )
L
11
-100~850 ( °C )
U
12
-200~400.0 ( °C )
23
-199.9~400.0 ( °C ) /-199.9~700.0
N
13
-200~1300 ( °C )
R
14
0~1700 ( °C )
S
15
0~1700 ( °C )
B
16
100~1800 ( °C )
10 °C -70 °C
17
0~90 ( °C )
60 °C -120 °C
18
0~120 ( °C )
115 °C -165 °C
19
0~165 ( °C )
140 °C -260 °C
20
0~260 ( °C )
0~50mV
21
One of the ranges below, depending
on the displayed results: -
1999~9999,
-199.9~999.9
4~20mA
0
0~20mA
1
-1999~9999
1~5V
2
-199.9~999.9
0~5V
3
-19.99~99.99
0~10V
4
-1.999~9.999
J, L: GB/T 4994-98
T, U: GB/T 2903-98
N: GB/T 17615-98
R : GB/T 1598-98
B: GB/T 2902-99
JPt100, Pt100:GB/T5977-99
Input temperature range
/-300~1500 ( °F )
( °F )
/0.0~210.0 ( °F )
( °F )
/0.0~210.0 ( °F )
/-300~2300 ( °F )
/-100~1500 ( °F )
/-300~700 ( °F )
( °F )
/0~1100 ( °F )
/-100~1500 ( °F )
/-300~700 ( °F )
( °F )
/-300~2300 ( °F )
/0~3000 ( °F )
/0~3000 ( °F )
/300~3200 ( °F )
/0~190 ( °F )
/0~240 ( °F )
/0~320 ( °F )
/0~500 ( °F )
Input indicator range
-200~870 ( °C )
/-340~1540 ( °F )
-199.9~520.0 ( °C ) /-199.9~940.0
( °F )
-20.0~120.0 ( °C ) /-40.0~250.0 ( °F )
-199.9~520.0 ( °C ) /-199.9~940.0
( °F )
-20.0~120.0 ( °C ) /-40.0~250.0 ( °F )
-220~1320 ( °C )
/-340~2340 ( °F )
-40.0~520.0 ( °C ) /-40.0~940.0 ( °F )
-120~870 ( °C )
/-140~1540 ( °F )
-40.0~420.0 ( °C ) /-40.0~790.0 ( °F )
-220~420 ( °C )
/-340~740 ( °F )
-199.9~420.0 ( °C ) /-199.9~740.0
( °F )
-20~620 ( °C )
/-40~1140 ( °F )
-120~870 ( °C )
/-140~1540 ( °F )
-220~420 ( °C )
/-340~740 ( °F )
-199.9~420.0 ( °C ) /-199.9~740.0
( °F )
-220~1320 ( °C )
/-340~2340 ( °F )
-20~1720 ( °C )
/-40~3040 ( °F )
-20~1720 ( °C )
/-40~3040 ( °F )
0~1820 ( °C )
/0~3240 ( °F )
-20~130 ( °C )
/-40~270 ( °F )
-20~160 ( °C )
/-40~320 ( °F )
-20~205 ( °C )
/-40~400 ( °F )
-20~300 ( °C )
/-40~580 ( °F )
-5 ~ 105% of the setting range
(however, display -1999 ~ 9999 or
-199.9 ~ 999.9)
-5 ~ 105% of the setting range
(however, display -1999 ~ 9999 or
-199.9 ~ 999.9)
Other than the decimal point's
numerical value range .

Advertisement

Table of Contents
loading

Table of Contents