Data Comparison
5-17-4 BLOCK COMPARE – BCMP(68)
Limitations
Description
Flags
174
Ladder Symbols
BCMP(68)
@BCMP(68)
CD
CB
R
Each lower limit word in the comparison block must be less than or equal to the
upper limit.
When the execution condition is OFF, BCMP(68) is not executed. When the exe-
cution condition is ON, BCMP(68) compares CD to the ranges defined by a block
consisting of of CB, CB+1, CB+2, ..., CB+31. Each range is defined by two
words, the first one providing the lower limit and the second word providing the
upper limit. If CD is found to be within any of these ranges (inclusive of the upper
and lower limits), the corresponding bit in R is set. The comparisons that are
made and the corresponding bit in R that is set for each true comparison are
shown below. The rest of the bits in R will be turned OFF.
CB ≤ CD ≤ CB+1
CB+2 ≤ CD ≤ CB+3
CB+4 ≤ CD ≤ CB+5
CB+6 ≤ CD ≤ CB+7
CB+8 ≤ CD ≤ CB+9
CB+10 ≤ CD ≤ CB+11
CB+12 ≤ CD ≤ CB+13
CB+14 ≤ CD ≤ CB+15
CB+16 ≤ CD ≤ CB+17
CB+18 ≤ CD ≤ CB+19
CB+20 ≤ CD ≤ CB+21
CB+22 ≤ CD ≤ CB+23
CB+24 ≤ CD ≤ CB+25
CB+26 ≤ CD ≤ CB+27
CB+28 ≤ CD ≤ CB+29
CB+30 ≤ CD ≤ CB+31
ER:
The comparison block (i.e., CB through CB+31) exceeds the data area.
Indirectly addressed DM word is non-existent. (Content of ∗DM word is
not BCD, or the DM area boundary has been exceeded.)
IR, SR, AR, DM, HR, TC, LR, #
CB: First comparison block word
CD
CB
R
IR, SR, AR, DM, HR, TC, LR
Bit 00
Bit 01
Bit 02
Bit 03
Bit 04
Bit 05
Bit 06
Bit 07
Bit 08
Bit 09
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Section 5-17
Operand Data Areas
CD: Compare data
IR, DM, HR, TC, LR
R: Result word