Memory Cassette Settings and Flags
9-1
Memory Cassettes
!
Caution
The C200HS will not operate properly unless the data for it is created on LSS version 3 or later. The
C200HS is not supported by earlier versions of the LSS.
!
Caution
Do not mount or remove a Memory Cassette without turning off the power supply to the C200HS
CPU.
9-2
Memory Cassette Settings and Flags
Word
Bit(s)
SR 269
00 to 07
08 to 10
11 to 13
14
15
386
The C200HS comes equipped with a built-in RAM for the user's program so pro-
grams can be created even without installing a Memory Cassette. An optional
Memory Cassette, however, can provide flexibility in handling program data, PC
Setup data, DM data, I/O comment data, and other IOM Area data. Memory Cas-
settes can be used for the following purposes.
• Saving, retrieving, and comparing data in the UM Area. This UM Area data can
include the user program, fixed DM data such as the PC Setup, expansion DM
data, I/O comment data, I/O table data, and UM Area allocation data.
• Automatically loading Memory Cassette data on PC startup.
• Saving and retrieving IOM Area data. IOM data includes IR 000 to IR 231, the
two work areas, the two SR Areas, the LR Area, the HR Area, the AR Area, the
TC Area, and DM 0000 to DM 6143.
There are two types of Memory Cassette available, each with a capacity of 16K
words. For instructions on installing Memory Cassettes, refer to the C200HS
Installation Guide.
The following table shows the Memory Cassettes used with C200HS PCs.
Memory
Capacity
EEPROM
16K words
EPROM
16K words
Note
1. Memory Cassettes for the C200HS cannot be used with the C200H, and
Memory Units for the C200H cannot be used with the C200HS.
2. EEPROM can be written up to 50,000 times. Data may be corrupted if this
limit is exceeded.
3. EPROM chips are sold separately.
The following settings and flags are available for Memory Cassettes in the SR
Area. Bits/words used in the procedures to manipulate Memory Cassettes are
described in the remainder of this section. Refer to page 46 for other details on
SR Area operation.
Memory Cassette Contents
Memory Cassette Capacity
Reserved by system (not accessible by user)
EEPROM Memory Cassette Protected or EPROM Memory Cassette Mounted Flag
Memory Cassette Flag
Model number
C200HS-ME16K
Can be written to while mounted in
the C200HS.
Can be used for both UM Area data
and IOM Area data.
A memory backup battery is not re-
quired.
C200HS-MP16K
Can be written with a commercially
available PROM writer.
Can be used for only UM Area data.
Function
00: Nothing; 01: UM; 02: IOM (03: HIS)
0: 0 KW (no board); 3: 16 KW
Section 9-2
Features

Hide quick links:

Advertisement

Table of Contents
loading