Data Conversion
5-18-10 ASCII CONVERT – ASC(86)
Limitations
Description
Digit Designator
194
Ladder Symbols
ASC(86)
@ASC(86)
S
Di
D
Di must be within the values given below
All destination words must be in the same data area.
When the execution condition is OFF, ASC(86) is not executed. When the exe-
cution condition is ON, ASC(86) converts the designated digit(s) of S into the
equivalent 8-bit ASCII code and places it into the destination word(s) beginning
with D.
Any or all of the digits in S may be converted in order from the designated first
digit. The first digit, the number of digits to be converted, and the half of D to re-
ceive the first ASCII code (rightmost or leftmost 8 bits) are designated in Di. If
multiple digits are designated, they will be placed in order starting from the des-
ignated half of D, each requiring two digits. If more digits are designated than
remain in S (counting from the designated first digit), further digits will be used
starting back at the beginning of S.
Refer to Appendix I for a table of extended ASCII characters.
The digits of Di are set as shown below.
Digit number: 3 2 1 0
Operand Data Areas
IR, SR, AR, DM, HR, TC, LR
S
IR, SR, AR, DM, HR, TC, LR, #
Di
D: First destination word
D
IR, SR, AR, DM, HR, LR
Specifies the first digit to be converted (0 to 3).
Number of digits to be converted (0 to 3)
0: 1 digit
1: 2 digits
2: 3 digits
3: 4 digits
First half of D to be used.
0: Rightmost 8 bits (1st half)
1: Leftmost 8 bits (2nd half)
Parity
0: none,
1: even,
2: odd
Section 5-18
S: Source word