Omron SYSMAC C200HS Operation Manual page 306

Programmable controllers
Hide thumbs Also See for SYSMAC C200HS:
Table of Contents

Advertisement

Network Instructions
SEND(90)/RECV(98) Enable Flag
00000
25204
12802
12801
12800
SEND(90)/RECV(98) Error Flag
12800
25203
12800
25204
00001
25204
12800
12803
12802
25204
25203
12802
SEND(90)/RECV(98) Error Flag
12802
25203
12802
25204
296
12800 prevents execution of SEND(90) until
S
RECV(98) (below) has completed. IR 00000
KEEP(11)
is turned ON to start transmission.
12800
R
@MOV(21)
#000A
DM 0000
@MOV(21)
#0000
DM 0001
Data is placed into control data words to
specify the 10 words to be transmitted to
@MOV(21)
node 3 in operating level 1 of network 00
#0003
(NSB).
DM 0002
XFER(70)
#0010
000
DM 0010
@SEND(90)
DM 0010
DM 0020
DM 0000
Turns ON to indicate transmission error.
00200
Resets 12800, above.
DIFU(13)
12801
S
12802 prevents execution of RECV(98)
KEEP(11)
when SEND(90) above has not completed.
IR 00001 is turned ON to start transmission.
12802
R
XFER(70)
Transmitted data moved into words
#0016
beginning at DM 0030 for storage.
000
DM 0030
@MOV(21)
#0010
DM 0003
Data moved into control data words to
@MOV(21)
specify the 16 words to be transmitted from
#0000
node 126 in operating level 1 of network 00
DM 0004
(NSB).
@MOV(21)
#007E
DM 0005
@RECV(98)
HR 10
LR 10
DM 0003
Turns ON to indicate reception error.
00201
Resets 12802, above.
DIFU(13)
12803
Section 5-26