Omron SYSMAC C200HS Operation Manual page 358

Programmable controllers
Hide thumbs Also See for SYSMAC C200HS:
Table of Contents

Advertisement

Monitoring Operation and Modifying Data
1, 2, 3...
Key Sequence
Example
350
Bit status will remain ON or OFF only as long as the key is held down; the original
status will return as soon as the key is released. If a timer is started, the comple-
tion flag for it will be turned ON when SV has been reached.
SHIFT and PLAY/SET or SHIFT and REC/RESET can be pressed to maintain
the status of the bit after the key is released. The bit will not return to its original
status until the NOT key is pressed, or one of the following conditions is met.
1. The Force Status Clear operation is performed.
2. The PC mode is changed. (See note.)
3. Operation stops due to a fatal error or power interruption.
4. The I/O Table Registration operation is performed.
This operation can be used in MONITOR mode to check wiring of outputs from
the PC prior to actual program execution. This operation cannot be used in RUN
mode.
Note The forced set/reset bit status will be maintained when switching from PRO-
GRAM to MONITOR mode if the Force Status Hold Bit is ON and DM 6601 of the
PC Setup has been set maintain the bit's status. Refer to 3-6-4 PC Setup for de-
tails.
The following example shows how either bits or timers can be controlled with the
Force Set/Reset operation. The displays shown below are for the following pro-
gram section.
00100
TIM 000
Address
Instruction
00200
LD
00201
TIM
00202
LD
00203
OUT
Data
00100
000
#
0123
TIM
000
00500
Section 7-1
TIM 000
012.3 s
#0123
00500