PC Setup
Word(s)
Bit(s)
DM 6648
00 to 07
08 to 11
12 to 15
DM 6649
00 to 07
08 to 15
Peripheral Port Settings (DM 6650 to DM 6654)
The following settings are effective after transfer to the PC.
DM 6650
00 to 07
08 to 11
12 to 15
DM 6651
00 to 07
08 to 15
DM 6652
00 to 15
DM 6653
00 to 07
08 to 11
12 to 15
Node number (Host link)
00 to 31 (BCD)
Start code enable (RS-232C)
0: Disable; 1: Set
End code enable (RS-232C)
0: Disable (number of bytes received)
1: Set (specified end code)
2: CR, LF
Start code (RS-232C)
00 to FF (binary)
12 to 15 of DM 6648 set to 0:
Number of bytes received
00: Default setting (256 bytes)
01 to FF: 1 to 255 bytes
12 to 15 of DM 6648 set to 1:
End code (RS-232C)
00 to FF (binary)
Port settings
00: Standard (1 start bit, 7-bit data, even parity, 2 stop bits, 9,600 bps)
01: Settings in DM 6651
Reserved
Communications mode
0: Host link; 1: RS-232C
Baud rate
00: 1.2K, 01: 2.4K, 02: 4.8K, 03: 9.6K, 04: 19.2K
Frame format
Start
Length
00:
1 bit
7 bits
01:
1 bit
7 bits
02:
1 bit
7 bits
03:
1 bit
7 bits
04:
1 bit
7 bits
05:
1 bit
7 bits
06:
1 bit
8 bits
07:
1 bit
8 bits
08:
1 bit
8 bits
09:
1 bit
8 bits
10:
1 bit
8 bits
11:
1 bit
8 bits
Transmission delay (Host Link)
0000 to 9999: In ms.
Node number (Host link)
00 to 31 (BCD)
Start code enable (RS-232C)
0: Disable; 1: Set
End code enable (RS-232C)
0: Disable (number of bytes received)
1: Set (specified end code)
2: CR, LF
Function
Stop
Parity
1 bit
Even
1 bit
Odd
1 bit
None
2 bit
Even
2 bit
Odd
2 bit
None
1 bit
Even
1 bit
Odd
1 bit
None
2 bit
Even
2 bit
Odd
2 bit
None
Appendix E
Default
0
Disabled
Disabled
Not used
Standard
---
Host Link
1.2 K
1 start bit, 7-bit
data, 1 stop bit,
even parity
0 ms
0
Disable
Disable
463