Monitoring Operation and Modifying Data
7-1-9
3-word Monitor
Key Sequence
Example
7-1-10 3-word Data Modification
Key Sequence
358
To monitor three consecutive words together, specify the lowest numbered
word, press MONTR, and then press EXT to display the data contents of the
specified word and the two words that follow it.
A CLR entry changes the Three-word Monitor operation to a single-word display.
Single-word monitor in progress
00000
00000
CHANNEL
D0000
89AB
D0002D0001D0000
0123 4567 89AB
D0003D0002D0001
ABCD 0123 4567
D0004D0003D0002
EF00 ABCD 0123
D0005D0004D0003
1111 EF00 ABCD
D0004D0003D0002
EF00 ABCD 0123
D0002
0123
This operation changes the contents of a word during the 3-Word Monitor opera-
tion. The blinking square indicates where the data can be changed. After the
new data value is keyed in, pressing WRITE causes the original data to be over-
written with the new data. If CLR is pressed before WRITE, the change operation
will be cancelled and the previous 3-word Monitor operation will resume.
This operation cannot be used to change SR 253 through SR 255. Only those
words displayed on the 3-word Monitor display can be changed.
3 words currently
displayed
Specify the first of the 3 words
DM 0000
you want to monitor.
Press the Up and Down Arrow
keys to change word addresses.
[ Data ]
Section 7-1