Error Flags
AR Area
Address(es)
0000 to 0009
Special I/O or PC Link Unit Error Flags
0010
SYSMAC LINK/SYSMAC NET Link Level 1 System Error Flags
0011
SYSMAC LINK/SYSMAC NET Link Level 0 System Error Flags
0012
Rack-mounting Host Link Unit Level 1 Error Flag
0013
Rack-mounting Host Link Unit Level 0 Error Flag
0014
Remote I/O Master Unit 1 Error Flag
0015
Remote I/O Master Unit 0 Error Flag
0200 to 0204
Error Flags for Slave Racks 0 to 4
0205 to 0215
Group-2 High-density I/O Unit Error Flags (AR 0205 to AR 0214 correspond to I/O numbers 0 to 9.)
0215
Group-2 High-density I/O Unit was not recognized.
0300 to 0315
Optical I/O Units (0 to 7) Error Flags
0400 to 0415
Optical I/O Units (8 to 15) Error Flags
0500 to 0515
Optical I/O Units (16 to 23) Error Flags
0600 to 0615
Optical I/O Units (24 to 31) Error Flags
0710 to 0712
Error Flags for Slave Racks 5 to 7
0713 to 0715
Error History Bits
1114
Communications Controller Error Flag Level 0
1115
EEPROM Error Flag for operating level 0
1514
Communications Controller Error Flag Level 1
1515
EEPROM Error Flag for operating level 1