Omron SYSMAC C200HS Operation Manual page 413

Programmable controllers
Hide thumbs Also See for SYSMAC C200HS:
Table of Contents

Advertisement

Host Link Commands
Response Format
1
x 10
x 10
@
Node no.
Parameters
11-3-3 HR AREA READ –– RH
Command Format
1
x 10
x 10
@
Node no.
Response Format
1
x 10
x 10
@
Node no.
Parameters
11-3-4 PV READ –– RC
Command Format
1
x 10
x 10
@
Node no.
Response Format
1
x 10
x 10
@
Node no.
Parameters
408
0
1
0
x 16
x 16
x 16
R
L
Header
End code
code
Read Data (Response)
The contents of the number of words specified by the command are returned in
hexadecimal as a response. The words are returned in order, starting with the
specified beginning word.
Reads the contents of the specified number of HR words, starting from the speci-
fied word.
0
3
2
x 10
x 10
x 10
R
H
Header
Beginning word
code
(0000 to 0099)
0
1
0
x 16
x 16
x 16
R
H
Header
End code
code
Read data (for number of words read)
Read Data (Response)
The contents of the number of words specified by the command are returned in
hexadecimal as a response. The words are returned in order, starting with the
specified beginning word.
Reads the contents of the specified number of timer/counter PVs (present val-
ues), starting from the specified timer/counter.
0
3
2
x 10
x 10
x 10
R
C
Header
Beginning timer/counter
code
(0000 to 0511)
0
1
0
x 16
x 16
x 10
R
C
Header
End code
code
Read data (for number of words read)
Read Data (Response)
The number of present values specified by the command is returned in hexade-
3
2
1
0
x 16
x 16
x 16
Read data (1 word)
Read data (for number of words read)
1
0
3
2
1
x 10
x 10
x 10
x 10
x 10
No. of words
(0001 to 0100)
3
2
1
0
x 16
x 16
x 16
Read data (1 word)
1
0
3
2
1
x 10
x 10
x 10
x 10
x 10
No. of timers/counters
(0001 to 0512)
3
2
1
0
x 10
x 10
x 10
Read data (1 word)
Section 11-3
:
FCS
Terminator
0
:
FCS
Terminator
:
FCS
Terminator
0
:
FCS
Terminator
:
FCS
Terminator

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents