Bit(s)
Startup Processing (DM 6600 to DM 6614)
The following settings are effective after transfer to the PC only after the PC is restarted.
DM 6600
00 to 07
Startup mode (effective when bits 08 to 15 are set to 02).
00: PROGRAM; 01: MONITOR 02: RUN
08 to 15
Startup mode designation
00: Programming Console switch
01: Continue operating mode last used before power was turned off
02: Setting in 00 to 07
DM 6601
00 to 07
Reserved
08 to 11
IOM Hold Bit (SR 25212) Status
0: Reset; 1: Maintain
12 to 15
Forced Status Hold Bit (SR 25211) Status
0: Reset; 1: Maintain
DM 6602
00 to 07
Reserved
08 to 15
Special I/O Unit Area
00: Use DM 1000 to DM 1999
01: Transfer DM 7000 through DM 7999 to DM 1000 through DM 1999 at
startup and use DM 1000 to DM 1999.
02: Use DM 7000 to DM 7999
DM 6603 to
00 to 15
Reserved
DM 6614
Cycle Time Settings (DM 6615 to DM 6619)
The following settings are effective after transfer to the PC the next time operation is started.
DM 6615
00 to 15
Reserved
DM 6616
00 to 07
(Servicing time for RS-232C port (effective when bits 08 to 15 are set to 01))
00 to 99 (BCD): Percentage of cycle time used to service RS-232C port.
Minimum: 0.256 ms; maximum 65.536 ms
08 to 15
(RS-232C port servicing setting enable)
00: Do not set service time
01: Use time in 00 to 07.
Service time is 10 ms when operation is stopped.
DM 6617
00 to 07
Servicing time for peripheral port (effective when bits 08 to 15 are set to 01)
00 to 99 (BCD): Percentage of cycle time used to service peripheral.
Minimum: 0.256 ms; maximum 65.536 ms
08 to 15
Peripheral port servicing setting enable
00: Do not set service time
01: Use time in 00 to 07.
Service time is 10 ms when operation is stopped.
DM 6618
00 to 07
Cycle monitor time (effective when bits 08 to 15 are set to 01, 02, or 03)
00 to 99 (BCD): Setting (see 08 to 15)
08 to 15
Cycle monitor enable (Setting in 00 to 07 x unit; 99 s max.)
00: 120 ms (setting in bits 00 to 07 disabled)
01: Setting unit: 10 ms
02: Setting unit: 100 ms
03: Setting unit: 1 s
DM 6619
00 to 15
Cycle time
0000: Variable (no minimum)
0001 to 9999 (BCD): Minimum time in ms
Appendix E
PC Setup
Function
Default
PROGRAM
Programming
Console switch
---
Reset
---
DM 1000 to
DM 1999
---
---
No setting (00)
No setting (00)
00
00: 120 ms
Variable
461