Variable Area (Setting Range) List - Omron E5CN-HT Communications Manual

Digital
Hide thumbs Also See for E5CN-HT:
Table of Contents

Advertisement

SECTION 3 Communications Data for CompoWay/F

3.1 Variable Area (Setting Range) List

For communications using a variable type not enclosed in parentheses in the following table, the set
value is double-word data (8 digits). For communications using a variable type enclosed in parentheses,
the set value is single-word data (4 digits).
For example, variable type C0 is double-word data (8 digits), and variable type 80 is single-word
data (4 digits).
Items expressed in hexadecimal in the "Set (monitor) value" column are the setting range for
CompoWay/F communications. The values in parentheses are the actual setting range. When there is a
section reference for a setting item, refer to that reference for details.
Variable
Address
Parameter name
type
C0 (80)
0000
Process Value
C0 (80)
0001
Status (See notes 1 and 2.)
C0 (80)
0002
Present SP
C0 (80)
0003
Heater Current 1 Value Monitor
C0 (80)
0004
MV Monitor (Heating)
C0 (80)
0005
MV Monitor (Cooling)
C0 (80)
0006
Heater Current 2 Value Monitor
C0 (80)
0007
Leakage Current 1 Monitor
C0 (80)
0008
Leakage Current 2 Monitor
C0 (80)
000A
Valve Opening Monitor
C0 (80)
000B
Remote SP Monitor
C0 (80)
000D
PID Set No. Monitor
C0 (80)
000E
Decimal Point Monitor (See note 1.)
C0 (80)
000F
Control Output 1 ON/OFF Count Moni-
tor
C0 (80)
0010
Control Output 2 ON/OFF Count Moni-
tor
C0 (80)
0011
Status 2 (See notes 1 and 2.)
C0 (80)
0012
Status (See notes 1 and 3.)
C0 (80)
0013
Status 2 (See notes 1 and 3.)
C0 (80)
0014
Program No. Monitor
C0 (80)
0015
Segment No. Monitor
C0 (80)
0016
Remaining Standby Time Monitor
C0 (80)
0017
Elapsed Program Time Monitor
C0 (80)
0018
Remaining Program Time Monitor
C0 (80)
0019
Elapsed Segment Time Monitor
C0 (80)
001A
Remaining Segment Time Monitor
C0 (80)
001B
Program Repetitions Monitor
C0 (80)
001C
SP Mode Setting Monitor
Note 1:
Not displayed on the Controller display.
Note 2:
When the variable type is 80 (word access), the rightmost 16 bits are read.
Note 3:
When the variable type is 80 (word access), the leftmost 16 bits are read.
Note 4:
If the Run/Reset parameter is set to Run, the current program number will be read.
If the Run/Reset parameter is set to Reset, the program number that is set in the Program No. parameter will be read.
3-2
Setting (monitor) value
Temperature: Use the specified range for each sensor.
Analog: Scaling lower limit −5% FS to Scaling upper limit +5% FS
See 3.2 Status and Status 2 for details.
SP lower limit to SP upper limit
H'00000000 to H'00000226 (0.0 to 55.0)
Standard: H'FFFFFFCE to H'0000041A (−5.0 to 105.0)
Heating/cooling: H'00000000 to H'0000041A (0.0 to 105.0)
H'00000000 to H'0000041A (0.0 to 105.0)
H'00000000 to H'00000226 (0.0 to 55.0)
H'00000000 to H'00000226 (0.0 to 55.0)
H'00000000 to H'00000226 (0.0 to 55.0)
H'FFFFFF9C to H'0000044C (−10.0 to 110.0)
SP Lower Limit to SP Upper Limit
H'00000001 to H'00000008 (1 to 8)
H'00000000 to H'00000003 (0 to 3)
H'00000000 to H'0000270F (0 to 9999)
H'00000000 to H'0000270F (0 to 9999)
Refer to 3.2 Status and Status 2.
Refer to 3.2 Status and Status 2.
Refer to 3.2 Status and Status 2.
H'00000000 to H'00000007 (0 to 7)
H'00000000 to H'0000001F (0 to 31)
H'00000000 to H'00009959 (hours, minutes)
H'00000000 to H'00009923 (days, hours)
H'00000000 to H'00009959
H'00000000 to H'00009959
H'00000000 to H'00009959
H'00000000 to H'00009959
H'00000000 to H'0000270F (0 to 9999)
H'00000000(0): Program SP mode
H'00000001(1): Remote SP mode
H'00000002(2): Fixed SP mode
Level
Operation
None
Operation
None
Advanced
function
setting
None
Operation
None
Operation
None