Parameters for Host Link and RS-232C Communications
PC Setup
Communications Procedure
Application Example
Plug:
XM2A-0901 (OMRON) or equivalent
Hood: XM2S-0901 (OMRON) or equivalent
C200HS
Signal
Abb.
FG
SD
RD
RS
CS
SG
Note Ground the FG terminals the C200HS to a resistance of 100 Ω or less.
To use a 1:1 link, the only settings necessary are the communications mode and
the link words. Set the communications mode for one of the PCs to the 1:1 mas-
ter and the other to the 1:1 slave, and then set the link words in the PC desig-
nated as the master. Bits 08 to 11 are valid only for the master for link one-to-one.
DM 6645: RS-232C port
Communications mode
Link words for one-to-one link
Port settings
If the settings for the master and the slave are made correctly, then the one-to-
one link will be automatically started up simply by turning on the power supply to
both the C200HSs and operation will be independent of the C200HS operating
modes.
This example shows a program for verifying the conditions for executing a one-
to-one link using the RS-232C ports. Before executing the program, set the fol-
lowing PC Setup parameters.
Master: DM 6645: 3200 (one-to-one link master; Area used: LR 00 to LR 15)
Slave: DM 6645: 2000 (one-to-one link slave)
The defaults are assumed for all other PC Setup parameters. The words used
for the one-to-one link are as shown below.
Master
LR00
Area for writing
LR07
LR08
Area for reading
LR15
Pin
No.
1
2
3
4
5
6
7
8
9
Bit
15
2: One-to-one link slave
3: One-to-one link master
0: LR 00 to LR 63
1: LR 00 to LR 31
2: LR 00 to LR 16
00: Standard communication parameters
Section 8-2
C200HS
Pin
Signal
No.
Abb.
1
FG
2
SD
3
RD
4
RS
5
CS
6
7
8
9
9
SG
0
Slave
LR00
Area for reading
LR07
LR08
Area for writing
LR15
383