SR Area
Data Link Status
38
SYSMAC LINK
Code
Item
00
Normal end
01
Parameter error
02
Unable to send
03
Destination not in
network
04
Busy error
05
Response timeout
06
Response error
07
Communications
controller error
08
Setting error
09
PC error
SYSMAC NET
Code
Item
00
Normal end
01
Parameter error
02
Routing error
03
Busy error
04
Send error (token
lost)
05
Loop error
06
No response
07
Response error
SR 238 to SR 245 contain the data link status for SYSMAC LINK/SYSMAC NET
Systems. The data structure depends on the system used to create the data link.
SYSMAC LINK
Operating
p
g
Operating
p
g
l
level 0
l 0
level 1
l
l 1
SR 238
SR 242
SR 239
SR 243
SR 240
SR 244
SR 241
SR 245
Leftmost bit
1: PC RUN status
1: PC CPU error
Meaning
Processing ended normally.
Parameters for network communication instruction is
not within acceptable ranges.
Unit reset during command processing or local node
in not in network.
Destination node is not in network.
The destination node is processing data and cannot
receive the command.
The response monitoring time was exceeded.
There was an error in the response received from
the destination node.
An error occurred in the communications controller.
There is an error in the node address settings.
An error occurred in the CPU of the destination
node.
Meaning
Processing ended normally.
Parameters for network communication instruction is
not within acceptable ranges.
There is a mistake in the routing tables for
connection to a remote network.
The destination node is processing data and cannot
receive the command.
The token was not received from the Line Server.
An error occurred in the communications loop.
The destination node does not exist or the response
monitoring time was exceeded.
There is an error in the response format.
Bit
12 to 15
11 to 08
Node 4
Node 3
Node 8
Node 7
Node 12
Node 11
Node 16
Node 15
1: Communica-
tions error
Section 3-4
04 to 07
00 to 03
Node 2
Node 1
Node 6
Node 5
Node 10
Node 9
Node 14
Node 13
Rightmost bit
1: Data link
operating

Hide quick links: