Long Message - Lmsg(47) - Omron SYSMAC C200HS Operation Manual

Programmable controllers
Hide thumbs Also See for SYSMAC C200HS:
Table of Contents

Advertisement

Special Instructions
Clearing Messages
Flags
Example
00000
00001
DM contents
DM 0010
4
1
DM 0011
4
3
DM 0012
4
5
DM 0013
4
7
DM 0014
4
9
DM 0015
4
B
DM 0016
4
D
DM 0017
4
F
5-25-5 LONG MESSAGE – LMSG(47)
Limitations
In handling indirectly addressed messages (i.e. :DM), those with the
lowest DM address values have higher priority.
To clear a message, execute FAL(06) 00 or clear it via a Programming Console
using the procedure in 4-6-5 Clearing Error Messages.
If the message data changes while the message is being displayed, the display
will also change.
Indirectly addressed DM word is non-existent. (Content of :DM word is
ER:
not BCD, or the DM area boundary has been exceeded.)
The following example shows the display that would be produced for the instruc-
tion and data given when 00000 was ON. If 00001 goes ON, a message will be
cleared.
ASCII
equivalent
4
2
A
B
4
4
C
D
4
6
E
F
4
8
G
H
4
A
I
J
4
C
K
L
4
E
M
N
5
0
O
P
Ladder Symbols
LMSG(47)
S
---
---
S through S+15 must be in the same data area and must be in ASCII. The mes-
sage will be truncated if a null character (00) is contained between S and S+15.
IR 298 and IR 299 cannot be used for S.
Address Instruction
MSG(46)
00000
DM 0010
00001
FAL(06) 00
00002
00003
MSG
ABCDEFGHIJKLMNOP
@LMSG(47)
S
---
---
Section 5-25
Operands
LD
MSG(46)
DM
LD
FAL(06)
Operand Data Areas
S: First source word (ASCII)
IR, SR, AR, DM, HR, TC, LR
---: Not used.
Set to 000
---: Not used.
Set to 000
00000
0010
00001
00
279