Omron SYSMAC C200HS Operation Manual page 261

Programmable controllers
Hide thumbs Also See for SYSMAC C200HS:
Table of Contents

Advertisement

Logic Instructions
5-22-3 LOGICAL OR – ORW(35)
Description
Example
Flags
Ladder Symbols
ORW(35)
@ORW(35)
I1
I2
R
When the execution condition is OFF, ORW(35) is not executed. When the ex-
ecution condition is ON, ORW(35) logically OR's the contents of I1 and I2
bit-by-bit and places the result in R.
15
I1
1
0
15
I2
0
1
15
1
1
R
Indirectly addressed DM word is non-existent. (Content of :DM word is
ER:
not BCD, or the DM area boundary has been exceeded.)
EQ:
ON when the result is 0.
IR, SR, AR, DM, HR, TC, LR, #
I1
IR, SR, AR, DM, HR, TC, LR, #
I2
R
0
1
1
0
0
1
1
0
1
0
1
0
1
0
0
1
1
1
0
1
1
Section 5-22
Operand Data Areas
I1: Input 1
I2: Input 2
R: Result word
IR, SR, AR, DM, HR, LR
00
0
0
1
1
0
0
1
00
1
0
1
0
1
0
1
00
1
0
1
1
1
0
1
251