Omron SYSMAC C200HS Operation Manual page 400

Programmable controllers
Hide thumbs Also See for SYSMAC C200HS:
Table of Contents

Advertisement

Error Messages
Error and message
High-density I/O Unit error
SYS FAIL FAL9A
PC Setup error
SYS FAIL FAL9B
Memory Cassette Transfer error
SYS FAIL FAL9D
Cycle time overrun
CYCLE TIME OVER
I/O table verification error
I/O VER ERR
Remote I/O error
REMOTE ERR
Remote I/O
Master Unit number
Special I/O Unit error
SIOU ERR
Group-2 High-density I/O error
SYS FAIL FAL 9A
Battery error
BATT LOW
394
FAL no.
9A
An error occurred in data
transfer between a
High-density I/O Unit and
the CPU.
9B
An error has been detected
in the PC Setup. This error
will be generated when the
setting is read or used for
the first time.
9D
An error has occurred
during data transmission
between UM and a Memory
Cassette because:
Not in PROGRAM Mode.
UM or Memory Cassette is
read-only.
Insufficient capacity in UM
or Memory Cassette.
A checksum error occurred
in the Memory Cassette
F8
Watchdog timer has
exceeded 100 ms.
E7
Unit has been removed or
replaced by a different kind
of Unit, making I/O table
incorrect.
B0 or B1
Error occurred in
transmissions between
*
Remote I/O Units.
D0
Error has occurred in PC
Link Unit, Remote I/O
Master Unit, between a
Host Link, SYSMAC LINK,
or SYSMAC NET Link Unit
and the CPU, or in refresh
between Special I/O Unit
and the CPU.
9A
An error has occurred
during data transmission
between the CPU and a
Group-2 High-density I/O
Unit.
F7
Backup battery is missing or
its voltage has dropped.
Probable cause
Check AR 0205 to AR 0214
to identify the Unit with a
problem, replace the Unit,
and restart the PC.
Check an correct PC Setup
settings.
Make sure that the PC is in
PROGRAM mode.
Make sure that the Memory
Cassette is not
write-protected.
Make sure that the UM and
Memory Cassette capacity
is sufficient.
Make sure that SYSMAC
NET data links are not
active during the transfer.
Transfer the data again.
Program cycle time is
longer than recommended.
Reduce cycle time if
possible.
Use I/O Table Verify
Operation to check I/O table
and either connect dummy
Units or register the I/O
table again.
Check transmission line
between PC and Master
and between Remote I/O
Units.
Determine the unit number
of the Unit which caused the
error (AR 00), correct the
error, and toggle the
appropriate Restart Bit in
AR 01, SR 250, or SR 252.
If the Unit does not restart,
replace it.
Determine the unit number
of the Unit which caused the
error (AR 02), replace the
Unit, and try to power-up
again.
Check battery, and replace
if necessary.
Section 10-4
Possible correction