Omron SYSMAC C200HS Operation Manual page 359

Programmable controllers
Hide thumbs Also See for SYSMAC C200HS:
Table of Contents

Advertisement

Monitoring Operation and Modifying Data
7-1-3
Forced Set/Reset Cancel
Key Sequence
The following displays show what happens when TIM 000 is set with 00100 OFF
(i.e., 00500 is turned ON) and what happens when TIM 000 is reset with 00100
ON (i.e., timer starts operation, turning OFF 00500, which is turned back ON
when the timer has finished counting down the SV).
(This example is performed in MONITOR mode.)
0010000500
^ OFF^ OFF
0010000500
=
ON^ OFF
Indicates that force set/reset is in progress.
0010000500
= OFF^ OFF
T0000010000500
^ OFF^ OFF
T0000010000500
0123^ OFF^ OFF
T0000010000500
=0000^ OFF^
ON
T0000010000500
0123^ OFF^ OFF
T0000010000500
o0000^
ON^
ON
T0000010000500
=0123^
ON^ OFF
T0000010000500
0122^
ON^ OFF
T0000010000500
o0000^
ON^
ON
Indicates that the time is up.
*Timing not done in PROGRAM mode.
This operation restores the status of all bits in the I/O, IR, TIM, CNT, HR, AR, or
LR areas which have been force set or reset. It can be performed in PROGRAM
or MONITOR mode.
When the PLAY/SET and REC/RESET keys are pressed, a beeper will sound. If
you mistakenly press the wrong key, then press CLR and start again from the
beginning.
Monitoring 00100 and 00500.
Force set bit status.
Reset the force-set bit.
Monitoring TIM 000.
Force setting TIM 000
turns ON 00500.
TIM 000 returns to its original status
when PLAY/SET is released.
Display with 0010 originally ON.
Timer starts timing, turning
00500 OFF.*
When the time is up, 00500
goes ON again.
Section 7-1
351