Omron SYSMAC C200HS Operation Manual page 70

Programmable controllers
Hide thumbs Also See for SYSMAC C200HS:
Table of Contents

Advertisement

DM Area
Parameter
Default
STARTUP MODE
STARTUP
Programming
MODE
Console
mode selector
FORCED
Don't hold
STATUS
IOM HOLD BIT
Don't hold
STATUS
CYCLE TIME
Variable
Detect Long
120 ms
Cycles
RS-232C SETUP
METHOD
Host link
NODE NO
0
DELAY
0
START CODE
None
END CODE
None
DATA LINK
None
AREAS
BAUD RATE
9,600 bps
STOP BITS
2 bits
PARITY
Even parity
DATA LENGTH 7 bits
PC SETUP, HEX
Used to set the above parameters on a binary display.
INPUT
The PC Setup is allocated to DM 6600 through DM 6655.
Settings
Programming Console
mode selector, previous
mode (i.e., the mode in
use last time power was
interrupted), PROGRAM,
MONITOR, or RUN
Hold or don't hold
Hold or don't hold
Variable or minimum
Minimum setting: 1 to
9,999 ms
0 to 99,000 ms
Host Link, RS-232C with
no protocol, 1:1 link
master, or 1:1 link slave
00 to 31
0 to 9,999 ms
00 to FF
00 to FF or CR, LF
LR 00 to LR 63, LR 00 to
LR 31, or LR 00 to LR 15
1200, 2400, 4800, 9600,
or 19200
1 or 2 bits
Even, odd, or none
7 or 8 bits
Remarks
Determines the operating mode the PC will start in
when power is turned ON.
This setting is required for restart continuation.
Setting is effective from next time power is turned on
to the PC.
Determines whether or not the status of the Forced
Status Hold Bit is maintained after power interruptions.
If the status of the Forced Status Hold Bit is not set to
be held, it will be turned OFF the next time the PC is
started and forced status will be cleared.
Setting is effective from next time power is turned on
to the PC.
Determines whether or not the status of the IOM Hold
Bit is maintained after power interruptions. If the status
of the IOM Hold Bit is not set to be held, it will be
turned OFF the next time the PC is started and I/O
status will be cleared.
This setting is required for restart continuation.
Setting is effective from next time power is turned on
to the PC.
Determines whether or not a minimum cycle time is to
be used for user program execution. If a minimum time
is set, the PC will wait until the minimum time has
expired before starting program execution again. The
entire program will be executed even if the minimum
time is exceeded.
This setting can be used to reduce variations in I/O
response times.
An error of approximately 3 to 4 ms, plus the execution
time required for any interrupt programs, can occur.
Setting is effective immediately.
If the set time is exceeded, the Cycle Time Exceeded
Flag will turn ON and a fatal error will occur.
An error of approximately 3 to 4 ms can occur.
Setting is effective immediately.
Determines the settings used when a device, such as
a Programmable Terminal or bar code reader is
connected to the RS-232C port.
Do not set the node number to a number already used
by another Unit connected in the same
by another Unit connected in the same
communications system (e.g., Host Link System). All
communications system (e.g., Host Link System). All
other settings must match those of the device being
other settings must match those of the device being
communicated with.
Settings are effective immediately.
S tti
ff
ti
i
Section 3-6
p
di t l
59