External Error Control Procedure; Procedure - KEB COMBIVERT F4-F Applications Manual

Hide thumbs Also See for COMBIVERT F4-F:
Table of Contents

Advertisement

Functional Description
6.6.3 External Error
Control

Procedure

Reaction to E. EF (Pn.20)
Chapter
Section
Page
6
6
4
With the external error control procedure units of other manufacturers can take direct
influence on the drive. In order to activate the error control procedure a digital input
di.3...di.12 must be assigned with the value „3". The behaviour at tripping of an external
fault is defined with Pn.20 according to following table:
Pn.20 Display Reaction
0
E. EF
Immediate disabling of modulation
1
A. EF
Quick stopping / disabling of modulation
after reaching speed 0
2
A. EF
Quick stopping / holding torque at speed 0
3
A. EF
Immediate disabling of modulation
4
A. EF
Quick stopping / disabling of modulation
after reaching speed 0
5
A. EF
Quick stopping / holding torque at speed 0
6
keine
No effect on the drive;
!Fault is being ignored!
Date
Name: Basis
08.03.99
KEB COMBIVERT F4-F
Keep on Running Functions
Restart
Remove fault;
Actuate reset
Automatic reset, if
the fault is no longer
present
- inapplicable -
©
KEB Antriebstechnik, 1999
All Rights reserved