Motor Name Plate; Motor Data From Name Plate (Dr.0; Motor Data From Name Plate - KEB COMBIVERT F4-F Applications Manual

Hide thumbs Also See for COMBIVERT F4-F:
Table of Contents

Advertisement

Motor Data and Controller Adjustment
6.5 Motor Data and
Controller
Adjustment

6.5.1 Motor Name Plate

Fig. 6.5.1
Example of a motor name plate
DK 160 L 4 F I
dr.0
3
dr.12
dr.3
50
Hz
ϕ
dr.4
cos
dr.1
U
FL
3
6.5.2 Motor Data from
Name Plate
(dr.0...dr.4, dr.12)
©
KEB Antriebstechnik, 1999
All Rights reserved
The adjustment of the correct motor data is important for a lot of inverter functions,
since this data is used for calculations which are needed by the inverter. Wrong settings
can cause control oscillations and uncontrollable behaviour of the drive.
KEB Antriebstechnik
GmbH & Co. KG
Schneeberg
ANTRIEBSTECHNIK
/TW150
96/1632804/ 001
-Mot IP
55
IM
B 3
VDE 053 0
15,0 KW
230/400
V
0,86
1455
230/400
V
~Mot
50
Hz
M
Br
Following parameters can be taken directly from the name plate (see above) and
entered:
- dr.0
Rated motor power
- dr.1
Rated motor speed
- dr.2
Rated motor current
- dr.3
Rated motor frequency
- dr.4
Rated motor output factor 0,05...1,00
- dr.12 Rated motor voltage
Parameter dr.2 and dr.12 must always be adjusted in accordance with the used
connection (star or delta). This means for the above motor name plate that it is
230 V / 48,5A for delta connection and 400 V / 28,5 A for star connection. It
doesn't matter that for example the rated output voltage of the inverter is larger
(see „87Hz-chracteristic").
Name: Basis
KEB COMBIVERT F4-F
Functional Description
Made in
Germany
W.KI.
F
/Y
49,5/28,5
A
1/min
IGR 05B
2500 Imp
5V D0/RS
Nm
I
Sp max
0,01...75kW
100...9999 U/min
0,1...1,1 x In.01 (delta / star connection)
20...300 Hz
100...500 V (delta / star connection)
ANTRIEBSTECHNIK
40
°C
127
kg
6xTTL
mm
Date
Chapter
Section
6
5
11.05.99
6
dr.2
Page