Control circuit
4.3.5.1 External supply
Using the external supply, the control board, I/Os, fieldbus, sensors (temperatures, humidity,
mounting orientation) and the internal fan remain in operation even if the power unit is discon-
nected.
U
Figure 20:
4.3.5.2 Digital outputs
All outputs are short-circuit proof. They are suitable for inductive loads (without free-wheeling
diode up to 300 mJ max.).
The sum of the load currents at the 24 V outputs of the control card (DO 0...DO 8, X2B.1/3...31
and X3A und X3B) must not exceed 3.4 A.
Figure 21:
Figure 22:
34
Uin
0Vin
External supply of the control board
I
L
max
DO 0...7
0V
Digital outputsDO 0...DO 7
I
L
max
DO 8
0V
Digital output DO 8
Input
Specification
Terminals
Current consumption:
Own use 0.65 A
+ load currents at DO 0 ... DO 8
+ load currents at X2B.1/3 ... 31
+ load currents at X3A and X3B
Specification
ILmax: 250 mA
Terminals
Specification
ILmax 2 A
Terminals
DO 8 X2A.34
Uin
U
: 24 V ±10 %
in
0Vin X2A.35
Uin X2A.36
U: 24 Vdc
DO
X2A.18/20...32
0...7
0 V X2A.17/19...31
U: 24 Vdc
0 V X2A.33